Every rule on this site names its source. This page collects them, so a reader can go to the document instead of trusting us.

The device

  • UL 943 — Ground-Fault Circuit-Interrupters. Class A 4–6 mA, the trip-time curve, miswire lock-out (2006), self-test (2015). The listing mark on every GFCI we sell.
  • UL 943C — Special-purpose GFCIs (Classes C, D, E) for 480 / 600 V industrial circuits.
  • UL 1699 — Arc-fault circuit interrupters. UL 1449 — Surge protective devices.
  • CSA C22.2 No. 144.1 — the Canadian GFCI standard, harmonized with UL 943; the c(UL)us or cCSAus mark covers both countries.

Where (the National Electrical Code, NFPA 70)

RuleWhat it coversSince
NEC 210.8(A) — dwelling unitsReceptacles (125 V through 250 V, 50 A or less since 2020) in bathrooms, garages and accessory buildings, outdoors, crawl spaces, unfinished basements, kitchens, sinks (within 6 ft), boathouses, bathtubs and showers (within 6 ft), laundry areas, and indoor damp or wet locations.Bathrooms 1975; outdoors 1973; kitchens 1987; basements 1990; laundry 2014; 250 V receptacles 2020
NEC 210.8(B) — other than dwelling unitsBathrooms, kitchens and areas with sinks, rooftops, outdoors, indoor damp or wet locations, locker rooms with showers, garages and service bays, crawl spaces, unfinished basements, laundry areas.Commercial kitchens 2008; broadened 2017 and 2020
NEC 210.8(F) — outdoor outlets, dwellingsOutdoor outlets supplied by single-phase branch circuits 150 V to ground or less, 50 A or less — including hard-wired equipment such as air-conditioner condensers (with a temporary exception for HVAC that most jurisdictions adopted).2020
NEC 406.4(D)(2) — replacements where no ground existsA non-grounding receptacle may be replaced with a GFCI receptacle (or a grounding-type one protected by a GFCI) marked "No Equipment Ground" — the Code's route to protection in two-wire homes.1993 (as 210-7(d))
NEC 422.5 — appliancesCertain appliances rated 150 V to ground or less and 60 A or less: automotive vacuums, drinking-water coolers and bottle-fill stations, high-pressure spray washers, tire inflators, vending machines, sump pumps, dishwashers (2020), and others as listed.Vending machines 2005; dishwashers 2014; broadened 2017 / 2020
NEC Article 680 — pools, spas, hot tubs, fountainsPump motors (2020: all, cord-connected or hard-wired), underwater luminaires above the low-voltage limit, receptacles within 20 ft of the water, spa and hot-tub equipment.Pool receptacles 1968 (the first GFCI rule); pump motors broadened 2020
  • 210.12 — AFCI protection (a different device).
  • 406.4(D)(3) — the "GFCI Protected" marking on downstream receptacles; 406.9 and 406.12 — WR and TR devices.
  • 590.6 — temporary installations: GFCI on 125 V, 15 / 20 / 30 A receptacles, listed cord sets accepted.

The workplace

RuleWhat it coversSince
OSHA 29 CFR 1926.404(b)(1) — constructionAll 120 V, single-phase, 15 A and 20 A receptacle outlets on construction sites that are not part of the permanent wiring: GFCI protection, or an assured equipment grounding conductor program. NEC 590.6 asks the same of temporary installations and adds the 30 A receptacles.OSHA 1981; NEC 590.6 (formerly 305-6) 1990s

29 CFR 1910.304(b)(3) carries a parallel rule for temporary wiring in general industry; NFPA 70E is the electrical-safety-in-the-workplace standard that references both.

The RCD world

RuleWhat it coversSince
IEC 61008 / 61009 / 61540 — RCDs, RCBOs, portable RCDsResidual-current devices for the 230 V world: 30 mA for additional protection, 10 mA where required, 100–300 mA for fire protection; types AC, A, F and B by the waveform detected.1990s; type F 2010s
  • IEC 61008 RCCBs · 61009 RCBOs · 61540 portable RCDs · 62423 Types F and B.
  • IEC 60364-4-41 — where 30 mA "additional protection" is required in an installation; BS 7671 (UK wiring regulations, 18th Edition) — the national version.

Editions and adoption

The NEC is revised every three years; a jurisdiction adopts an edition on its own schedule and may amend it. Where this site says "since 2020", it means the 2020 edition of the NEC; whether that binds you depends on what your state or city adopted. UL standards apply to the product at the date of manufacture.