Where ground-fault protection is required

13 of the 14 places below require it under the edition of the Code most of the country enforces. The rule and the year are on every row; the reasoning is in the room-by-room guide. Your inspector's edition binds — states adopt the 2017, 2020 and 2023 editions on their own schedules.

LocationGFCIRuleNote
BathroomRequiredNEC 210.8(A) — dwelling unitsEvery receptacle.
Kitchen countertopRequiredNEC 210.8(A) — dwelling unitsCountertop receptacles since 1987; 2023 extends to every kitchen receptacle in many adoptions.
Within 6 ft of a sinkRequiredNEC 210.8(A) — dwelling unitsMeasured from the top inside edge of the bowl.
Laundry areaRequiredNEC 210.8(A) — dwelling unitsSince 2014.
Garage and accessory buildingsRequiredNEC 210.8(A) — dwelling unitsThe old exemptions for a dedicated freezer or garage-door receptacle are gone.
OutdoorsRequiredNEC 210.8(A) — dwelling unitsReceptacles; and since 2020 outdoor outlets generally (210.8(F)).
Unfinished basementRequiredNEC 210.8(A) — dwelling unitsFinished basements: the rooms' own rules apply.
Crawl spaceRequiredNEC 210.8(A) — dwelling unitsAt or below grade.
Within 6 ft of a bathtub or showerRequiredNEC 210.8(A) — dwelling unitsOutside the bathroom too.
BoathouseRequiredNEC 210.8(A) — dwelling units
Pool, spa, hot tub, fountainRequiredNEC Article 680 — pools, spas, hot tubs, fountainsPump motors, lighting, receptacles within 20 ft.
Living room, bedroom, hallwayNot by 210.8NEC 210.8(A) — dwelling unitsNot required by 210.8 (AFCI protection is, in most adoptions — a different device).
Construction site temporary powerRequiredOSHA 29 CFR 1926.404(b)(1) — constructionOSHA, not the NEC: GFCI or an assured grounding program.
Commercial kitchen, sink area, rooftop, service bayRequiredNEC 210.8(B) — other than dwelling unitsNon-dwelling list; check the edition your jurisdiction adopted.

The rules behind the table

NEC 210.8(A) — dwelling units

Receptacles (125 V through 250 V, 50 A or less since 2020) in bathrooms, garages and accessory buildings, outdoors, crawl spaces, unfinished basements, kitchens, sinks (within 6 ft), boathouses, bathtubs and showers (within 6 ft), laundry areas, and indoor damp or wet locations.

Since: Bathrooms 1975; outdoors 1973; kitchens 1987; basements 1990; laundry 2014; 250 V receptacles 2020 · Where the NEC requires GFCI protection, room by room

NEC 210.8(B) — other than dwelling units

Bathrooms, kitchens and areas with sinks, rooftops, outdoors, indoor damp or wet locations, locker rooms with showers, garages and service bays, crawl spaces, unfinished basements, laundry areas.

Since: Commercial kitchens 2008; broadened 2017 and 2020 · Where the NEC requires GFCI protection, room by room

NEC 210.8(F) — outdoor outlets, dwellings

Outdoor outlets supplied by single-phase branch circuits 150 V to ground or less, 50 A or less — including hard-wired equipment such as air-conditioner condensers (with a temporary exception for HVAC that most jurisdictions adopted).

Since: 2020 · GFCI outdoors, in garages, basements and crawl spaces

NEC Article 680 — pools, spas, hot tubs, fountains

Pump motors (2020: all, cord-connected or hard-wired), underwater luminaires above the low-voltage limit, receptacles within 20 ft of the water, spa and hot-tub equipment.

Since: Pool receptacles 1968 (the first GFCI rule); pump motors broadened 2020 · GFCI for pools, spas and hot tubs: Article 680

NEC 422.5 — appliances

Certain appliances rated 150 V to ground or less and 60 A or less: automotive vacuums, drinking-water coolers and bottle-fill stations, high-pressure spray washers, tire inflators, vending machines, sump pumps, dishwashers (2020), and others as listed.

Since: Vending machines 2005; dishwashers 2014; broadened 2017 / 2020 · GFCI for food service and wash-down floors

NEC 406.4(D)(2) — replacements where no ground exists

A non-grounding receptacle may be replaced with a GFCI receptacle (or a grounding-type one protected by a GFCI) marked "No Equipment Ground" — the Code's route to protection in two-wire homes.

Since: 1993 (as 210-7(d)) · GFCI in older homes without a ground wire

OSHA 29 CFR 1926.404(b)(1) — construction

All 120 V, single-phase, 15 A and 20 A receptacle outlets on construction sites that are not part of the permanent wiring: GFCI protection, or an assured equipment grounding conductor program. NEC 590.6 asks the same of temporary installations and adds the 30 A receptacles.

Since: OSHA 1981; NEC 590.6 (formerly 305-6) 1990s · GFCI on construction sites: the OSHA rule and how contractors meet it

UL 943 — the GFCI product standard

Class A trip 4–6 mA; trip time within 25 ms at 250 mA of fault current (the inverse-time curve); self-test and lock-out for receptacle GFCIs since June 2015; reverse-line-load miswire protection.

Since: 1976 (first edition); self-test 2015 · The standards behind every rule on this site

IEC 61008 / 61009 / 61540 — RCDs, RCBOs, portable RCDs

Residual-current devices for the 230 V world: 30 mA for additional protection, 10 mA where required, 100–300 mA for fire protection; types AC, A, F and B by the waveform detected.

Since: 1990s; type F 2010s · RCD types AC, A, F and B: what each one can see